Shunt Trip Breaker TRMF2-125T MCCB 125Frame/3P 15A up to 125A
Shunt Trip Breakers TRMF2-125T MCCB 125Frame/3P 15A up to 125
A shunt-trip breaker, in addition to the internal instantaneous overcurrent and time-overcurrent protective functions, has an externally powered solenoid that will trip the breaker when energized. This is normally tied to a safety interlock system that will shut power off to the affected equipment when, for example, a protective cover is opened or removed. A limit switch or other similar device will be used to detect if the cover is in place or not. It is held open by the cover. If the switch closes, the breaker is tripped and the machine is rendered electrically safe.
For bulk purchasing, please email to : info@electric-b2c.com
TRM series circuit breaker and auxiliaries comply with the following international standard:
1.IEC/EN 60947-1
Low-voltage switchgear and controlgear-part 1: General rules;
2.IEC/EN 60947-2
Low-voltage switchgear and controlgear-part 2: Circuit breakers;
1. Ambient temperature: Within the range of -5ºC--+55ºC(However, when the temperature exceed 40ºC,it should be considered to reduce the capacity to use);
2. Relative humidity: Within the range of 45%--85%;
3. Altitude: 2000m or less(However, if it exceeds 1000m, atmosphere correction through humidity test and withstand voltage test can be considered);
4. Atmosphere where excessive steam, oil steam, smoke, dust, salt and other corrosive materials do not exist;
Classification:
According to the poles: 2-poles, 3-poles
According to the breaking capacity: S-type, H-type
According to the rated current: Fix type, Adjustable type(08In-1.0In)
Technical data table:
Ampere frame size | TRMF2(125A) | ||||||||
Breaking capacity code | S | H | |||||||
Product code and poles | 1P | 2P | 3P | 4P | 1P | 2P | 3P | 4P | |
TRMF2-S1 | TRMF2-S2 | TRMF2-S3 | TRMF2-S4 | TRMF2-H1 | TRMF2-H2 | TRMF2-H3 | TRMF2-H4 | ||
Rated current, In(A) | 15, 20, 30, 40, 50, 60, 75, 80, 100, 125 | ||||||||
Adjustable part | Rated current setting(0.8In-1.0In) | χ | √ | √ | √ | χ | √ | √ | √ |
Lockup device for operating handle | χ | √ | √ | √ | χ | √ | √ | √ | |
Rated operational voltage, Ue(V), AC 50/60 Hz | 240/415 | ||||||||
Rated insulation voltage, Ui(V) | 1000 | ||||||||
Rated impulse withstand voltage, Uimp(kV) | 8 | ||||||||
Standard | Conformity with IEC/EN 60947-2 | ||||||||
Rated frequency(Hz) | 50/60 | ||||||||
Rated short-circuit breaking capacity, Icu(kA) | |||||||||
AC | 240V | 18 | 35 | 25 | 50 | ||||
415V | - | 18 | - | 35 | |||||
Ics=% * Icu | 50% | 100% | 50% | 100% | |||||
Mechanical life(circle) | 8500 | ||||||||
Electrical life(circle) | 1500 | ||||||||
Dimension: Length*Width*Height |
1-pole | 130*25*60 | |||||||
2-poles | 130*50*60 | ||||||||
3-poles | 130*75*60 | ||||||||
4-poles | 130*100*60 |
remote control circuit breaker,Shunt Trip Breaker,Shunt Trip Circuit Breaker,fire alarm circuit breaker
Built-in accessory:
Built-out accessory: